Description
Input
-
Voltage: 208/220/230/240 VAC
-
Frequency: 50/60 Hz
-
Voltage range: 90–300 VAC ±3 VAC
-
Frequency range: 40–70 Hz ±0.5 Hz
-
Power factor: 0.99
-
Bypass voltage range: 115–285 VAC
Batteries and Charger
-
Internal: 16 batteries of 12 V / 9 Ah (VRLA)
-
Recharge time: 5 hours to 90%
Output
-
Voltages: 208/220/230/240 VAC and 100/110/120/127 VAC
-
Waveform: Pure sine wave
-
THD: ≤2% (linear loads) / ≤7% (non-linear loads)
-
Frequency: 50/60 Hz ±4% (synchronous mode) / ±1% (independent mode)
-
Overload: 105–125% (60 s), 125–150% (30 s)
-
Efficiency: 92%
Bypass
-
Static + maintenance (manual)
Communications
-
RS-232 (standard) | USB / SNMP (optional)
Alarms and Events
-
AC/DC input, overload, inverter, low battery, fan failure
Protections
-
Input/output overvoltage or undervoltage, overload, overheating, short circuit
Environmental Conditions
-
Audible noise: 55 dB
-
Operating temperature: -10 to +40 °C
-
Relative humidity: 0–97% non-condensing
-
Altitude: 1000 m
-
Storage temperature: -15 to +45 °C
Standards and Compliance
-
Safety: IEC 62040-1
-
EMC:
-
ESD IEC 61000-4-2 Level 4
-
RS IEC 61000-4-3 Level 3
-
EFT IEC 61000-4-4 Level 4
-
Surge IEC 61000-4-5 Level 4
-
Mechanical (reference)
-
Compact tower / rack 8–12 U (depending on version)
-
Approx. dimensions: 300 × 700 × 900 mm | Weight: 55–70 kg
Hospital Functions
-
Night silent mode
-
Stabilized output for monitors/ventilators
-
Relays for BMS