Description
Input
-
208/220/230/240 VAC | 50/60 Hz | PF 0.99, THDi ≤3% (typical)
Batteries and Charger
-
External VRLA / LiFePO₄ banks | 240–384 Vdc bus (depending on configuration)
-
High-efficiency modular charger (adjustable current)
Output
-
208/220/230/240 VAC | THD ≤2% (linear loads) / ≤5% (non-linear loads)
-
Crest factor: 3:1
-
Efficiency: 95% (double conversion) | ECO mode up to 98%
-
Overload: 125% (10 min), 150% (1 min)
Bypass
-
Internal static + front maintenance (safe hot-swap)
Communications
-
RS-232 / USB | SNMP, Modbus, BACnet (optional) | dry contacts
Environmental Conditions
-
Noise: ≤62 dB
-
Temperature: 0–40 °C
-
Relative humidity: 0–95%
-
Hospital-grade EMI/RFI filters
Standards
-
IEC/EN 62040-1/2, IEC 61000-4-5 (Surge), UL (depending on variant)
Mechanical (reference)
-
19″ Modular cabinet | 600 × 1000 × 1200 mm | 180–230 kg (depending on modules)