Input
-
Input voltage: 208/220/230/240 VAC (3Φ)
-
Nominal frequency: 50/60 Hz
-
Frequency range: 46–54 Hz (50 Hz mode) / 56–64 Hz (60 Hz mode)
-
Input power factor: 0.99
-
THDi (typical): ≤5% (with active PFC)
Batteries and Charger
-
Architecture: VRLA or LiFePO₄ banks (optional)
-
Recharge time: 5 hours to 90% capacity
-
Smart DC charger, programmable maximum current (temperature-managed)
Output
-
Voltages: 208/220 VAC and 120/127 VAC
-
Waveform: Pure sine wave
-
THD: ≤2% linear loads / ≤7% non-linear loads
-
Output frequency: 50/60 Hz ±1% (independent mode)
-
Overload capability: 100–110% (60 min), 110–125% (10 min), 125–150% (1 min), >150% instantaneous
-
Efficiency: 92% (double conversion), optional ECO mode
Bypass
-
Static (uninterruptible transfer) + maintenance bypass (mechanical)
Communications
-
RS-232 (standard) | USB, RS-485/Modbus, SNMP (optional) | Dry contacts
Alarms and Events
-
AC/DC input, overload, inverter, low battery, active bypass
-
Event logging and self-diagnostics
Protections
-
Over/under voltage (input/output), overload, overtemperature, short circuit
-
Cold start, safe start sequence
Environmental Conditions
-
Audible noise: 70 dB
-
Operating temperature: 0–40 °C
-
Relative humidity: 95% non-condensing
-
Altitude: 1000 m (no derating)
-
Storage temperature: -15 to +45 °C
Standards and Compliance
-
IEC/EN 62040-1 (safety), IEC/EN 62040-2 Cat. C3 (EMI)
-
EMS/EMC:
-
IEC/EN 61000-4-2 (ESD, Level 4)
-
IEC/EN 61000-4-3 (RS, Level 3)
-
IEC/EN 61000-4-4 (EFT, Level 4)
-
IEC/EN 61000-4-5 (Surge, Level 4)
-
IEC/EN 61000-4-6 (CS)
-
IEC/EN 61000-4-8 (Level 4)
-
IEC/EN 61000-2-2
Note: Equivalent corrections listed according to IEC 61000-x-x notation
-
Mechanical (reference)
-
Hospital-grade cabinet with EMI/RFI filters, leveling wheels
-
Approx. dimensions: 650 × 900 × 1350 mm | Weight: 220–260 kg
Hospital Functions
-
Low electrical noise emission
-
0 ms transfer time
-
Solid neutral
-
Bypass lock for operating room (configurable)
-
Dry contacts for BMS