UPS VenusSafe 6KVA — Hospital UPS 6 kVA, Single-Phase, Online Double Conversion

LV6K

Capacity / Real Power: 6 kVA / 5.4 kW
Topology: Online double conversion (IGBT rectifier)
Typical Applications: ICU, monitors, critical racks, laboratory

Category:

Description

Input

  • Voltage: 208/220/230/240 VAC

  • Frequency: 50/60 Hz

  • Voltage range: 90–300 VAC ±3 VAC

  • Frequency range: 40–70 Hz ±0.5 Hz

  • Power factor: 0.99

  • Bypass voltage range: 115–285 VAC


Batteries and Charger

  • Internal: 16 batteries of 12 V / 9 Ah (VRLA)

  • Recharge time: 5 hours to 90%


Output

  • Voltages: 208/220/230/240 VAC and 100/110/120/127 VAC

  • Waveform: Pure sine wave

  • THD: ≤2% (linear loads) / ≤7% (non-linear loads)

  • Frequency: 50/60 Hz ±4% (synchronous mode) / ±1% (independent mode)

  • Overload: 105–125% (60 s), 125–150% (30 s)

  • Efficiency: 92%


Bypass

  • Static + maintenance (manual)


Communications

  • RS-232 (standard) | USB / SNMP (optional)


Alarms and Events

  • AC/DC input, overload, inverter, low battery, fan failure


Protections

  • Input/output overvoltage or undervoltage, overload, overheating, short circuit


Environmental Conditions

  • Audible noise: 55 dB

  • Operating temperature: -10 to +40 °C

  • Relative humidity: 0–97% non-condensing

  • Altitude: 1000 m

  • Storage temperature: -15 to +45 °C


Standards and Compliance

  • Safety: IEC 62040-1

  • EMC:

    • ESD IEC 61000-4-2 Level 4

    • RS IEC 61000-4-3 Level 3

    • EFT IEC 61000-4-4 Level 4

    • Surge IEC 61000-4-5 Level 4


Mechanical (reference)

  • Compact tower / rack 8–12 U (depending on version)

  • Approx. dimensions: 300 × 700 × 900 mm | Weight: 55–70 kg


Hospital Functions

  • Night silent mode

  • Stabilized output for monitors/ventilators

  • Relays for BMS